Free · No Login · Works On Site
728×90 Ad — Google AdSense Leaderboard
🔌
Ohm's Law
V = I × R

Fill in any two values — the third is calculated.

Result
💡
Power (Watts)
P = V × I

Fill in any two values — the third is calculated.

Result
📐
kVA ↔ kW Converter
kW = kVA × PF

Fill in any two to get the third.

Result
〰️
Single Phase Current
I = kW×1000 / (V×PF)
Full Load Current
Amps (A)
🔺
Three Phase Current
I = kW×1000 / (√3×V×PF)
Full Load Current
Amps (A) per phase
🔋
MCB / Fuse Size
In ≥ Ib
Minimum Breaker
🔌
Cable Size Calculator
It ≥ In / (Ca×Cg×Cc×Ci)

Calculates minimum cable CSA using BS 7671 Appendix 4 correction factors. Covers T&E (flat twin), SWA, and flex.

Recommended Minimum Cable Size
📉
Voltage Drop Calculator
Vd = (mV/A/m × I × L) / 1000
Voltage Drop
🔵
Conduit Fill Calculator
Fill ≤ 40% of conduit CSA

BS 7671 requires cables to fill no more than 40% of the conduit internal CSA to allow cables to be drawn in without damage.

Cable groups (number of each)

Fill Result
🔄
Ring Main Load Check
Ib ≤ 20A · Floor Area ≤ 100m²

A standard 32A ring final circuit in a domestic property. Check total load and floor area compliance.

Ring Circuit Assessment
🔌
Spur Assessment
Sockets on spur ≤ 1

Check if a spur off a ring circuit is within the limits of BS 7671 and GN3.

Spur Assessment
🌍
Prospective Fault Current
Isc = V / Zs
Prospective Fault Current
⚙️
Motor Starting Current
Istart ≈ FLC × Mult
Starting Current
💰
Running Cost Calculator
Cost = kWh × Rate
Annual Running Cost
📐
Max Demand Calculator
Pmax = Σ(P × DF)

Estimate the maximum demand for a domestic or small commercial installation.

Maximum Demand
Common Formulas
FormulaDescriptionVariables
V = I × ROhm's Law — VoltageV=Volts, I=Amps, R=Ohms
P = V × ISingle phase powerP=Watts
P = I² × RPower from current & resistance
I = P / (√3 × V × PF)3-phase full load current√3 ≈ 1.732
Vd = (mV/A/m × Ib × L) / 1000Voltage drop (BS 7671 method)L in metres
It ≥ In / (Ca×Cg×Cc×Ci)Cable tabulated current neededCorrection factors
Isc = Vp / ZsProspective fault currentZs = loop impedance
kW = kVA × PFReal vs apparent powerPF = power factor
E = P × t / 1000Energy (kWh)P=Watts, t=hours
cos φ = kW / kVAPower factor angleφ = phase angle
BS 7671 Max Zs Values — Common Devices
DeviceRatingMax Zs (Ω) — 0.4sMax Zs (Ω) — 5s
Type B MCB6A7.67
Type B MCB16A2.87
Type B MCB20A2.30
Type B MCB32A1.44
Type C MCB16A1.44
Type C MCB32A0.72
Type D MCB16A0.72
BS 88 fuse32A1.091.84
BS 88 fuse63A0.470.82
30mA RCDAny1667Ω max
Standard Cable Current Ratings (70°C PVC, Clipped Direct)
CSA2-core (A)3-core (A)Max V-drop (mV/A/m)
1.0mm²14.513.536.2
1.5mm²18.517.524.0
2.5mm²252315.0
4.0mm²32309.5
6.0mm²43386.4
10mm²57523.8
16mm²75682.4
25mm²96871.5
35mm²1191071.15
50mm²1501340.87
70mm²1851680.63
95mm²2322100.47
Minimum Earth Conductor Sizes (BS 7671 Table 54.7)
Phase/Line ConductorMin CPC (same material)Min CPC (different material)
≤16mm²Same CSA as phaseEquivalent conductance
16mm² – 35mm²16mm²Equivalent conductance
>35mm²Half the phase CSAEquivalent conductance
728×90 Ad — Google AdSense Leaderboard